How to wire a heat pump electrically?
The electrical connection of a heat pump in Quebec must comply with the rules in sections 28 (motors) and 62 (heating equipment) of the Code:
For a wall heat pump (mini-split):
- Voltage: 208/240 V single-phase
- Breaker: 15 A or 20 A depending on the outdoor unit's FLA
- Conductor: #14 AWG or #12 AWG, AC90 or TECK90 cable
- Disconnect: 30 A visible and accessible next to the outdoor unit
- GFCI is not required for a dedicated heat pump circuit
For a central heat pump (air-to-air or geothermal):
- Breaker: 30 A to 60 A depending on the model
- Conductor: #10 AWG to #6 AWG
- Backup heating (resistance): May require a second 50 A circuit if the heat pump is not designed for extreme cold
Since 2024, the Construction Code requires all new heating/cooling equipment to comply with Quebec's energy efficiency regulations.